ANGREEN Silane self-crosslinking XLPO material for building electrical wiring can be used to manufacture various types of building wires—such as BVJ and EI5 types—that comply with international standards like IEC 60754-2 and EN 50525. It undergoes natural crosslinking (curing) at ambient temperature.
| Brand number | GW-BYJ-01 | Category | XLPE/PO |
| Temperature rating | 105℃ | Color | Full color range |
| Crosslinking method | Silane Cross-linked | ||
| Appearance | Pellets | Processing Method | Extrusion |
| Product Features | Halogen-free, low smoke emission, long-term aging resistance, easy processability, wear resistance, and compliance with ROHS and REACH requirements. | ||
| Application Scope | EI5,Constructionfabrics, wires, etc.. | ||
| GW-GF-02 | Material A: GW-BYJ-01(A), Material B: GW-BYJ-01(B),mix the two evenly in a 95/5 ratio. | ||
| Physical Properties | ||||
| Property | Requirement | Typical Value | Unit | Test method |
| Density | 1.45-1.55 | 1.5 | g/cm3 | ISO 1183 |
| Hardness at 15" | 95±3 | 95 | Shore A | ISO 868 |
| Tensile Strength | ≥ 10 | 12.5 | Mpa | ISO 527 |
| Elongation at break | ≥ 125 | 180 | % | ISO 527 |
| Thermal elongation 0.2MPa×200℃×15min | ||||
| Elongation under load | ≤ 100 | 30-40 | % | GB/T 2951 |
| Permanent deformation | ≤25 | 0 | % | GB/T 2951 |
| Aging performance 136℃×168h | ||||
| Change rate of tensile strength | ≤±30 | 15 | % | GB/T2951.12 |
| Change rate of elongation at break | ≤±30 | -10 | % | GB/T2951.12 |
| Impact brittlement temperature(-40 ºC) | ≤ 15/30 | 0/30 | PCS | GB/T 5470 |
Volume Resistivity20℃ (Alternating Polarity Method) | ≥1*10^14 | 2.0*10^14 | Ω .cm | ASTM D257 |
| Dielectric strength | ≥20 | 25 | MV/m | DIN EN 6024 |
| Flame Retardant Properties | ||||
| LOI | ≥30 | 35 | % | GB/T2406 |
| Smoke density (flamed) | Ds max | 90 | / | GB/T8627 |
| Halogen-Free Properties | ||||
| Property | Requirement | Typical value | Unit | Test method |
| Halogen gas content | ≤5.0 | 0 | mg/g | IEC60754-2 |
| PH | ≥4.3 | 4.9 | / | IEC60754-2 |
| Electrical conductivity | ≤ 10 | 0.61 | us/mm | IEC60754-2 |